Customer Service & Support: +49 2452 962-450

Business inquiries: +49 2452 962-400

Mon – Fri: 8:00 – 17:00 (CET)

Anemometer-sensor TS 410 SDI
  1. Products & Services
  2. Measuring devices
  3. Multifunction
  4. T3000
  5. SDI sensors
  6. Anemometer sensors
  7. TS 410 SDI

Anemometer Sensor TS 410 SDI

Anemometer sensor for the T3000 multifunctional meter

Multifunctionality at its best

The innovative concept of a universal base device T3000, which is supplemented with flexibly exchangeable sensors , frees users from the need to always carry a complete collection of individual measuring devices with them for their measuring jobs.

A simple sensor change transforms your T3000 into exactly the special measuring device that you currently need. No further settings are required on the device because the intelligent technology of the T3000 automatically recognizes the connected sensor.

This sensor is not only suitable for checking the distribution of flow and temperature in ventilation and air conditioning systems but also for finding weak points when certifying the air tightness of buildings (blower door).

Reconstruction companies also use it to check the capacity of their drying installations in insulation layer drying after water damage as the TS 410 SDI allows them to quickly and precisely determine whether there is sufficient flow of air at the relief openings to dry out the insulation layer.

All SDI sensors in direct comparison:

To find the SDI-Sensor which exactly meets your requirements, please consult the concise overview of all SDI sensors from Trotec, which we're providing to you here so that you can compare them directly to each other.

Models which you do not wish to include in your comparison can be easily dismissed with only one click.

Technical data by comparison


TS 410 SDI TS 430 SDI TS 470 SDI
Display 1: air flow rate
Measuring range air flow: 0.00 to 20.00 m/s 0.00 to 2.00 m/s 0.00 to 20.00 m/s
Air flow resolution: 0.01m/s 0.01m/s 0.01m/s
Air flow accuracy: ± (0.2 m/s + 2% of reading) ± (0.04 m/s + 1% of reading) ± (0.2 m/s + 3% of reading)
Units for air flow/volume flow display: m/s, m³/s, m³/min, m³/h, l/min m/s, m³/s, m³/min, m³/h, l/min m/s, m³/s, m³/min, m³/h, l/min




Display 2: Temperature
Measuring range temperature 0 °C to +50 °C 0 °C to +50 °C 0 °C to +50 °C
Resolution temperature: 0,1 °C 0,1 °C 0,1 °C
Accuracy temperature: ± 0.7 °C (at v > 0.5 m/s) ± 0.7 °C (at v > 0.5 m/s) + 1.0 °C (at v > 0.5 m/s)
Temperature display units °C, °F °C, °F °C, °F
sensor element
material stainless steel stainless steel polycarbonate
length Ø: 210 mm / 6 mm Ø: 210 mm / 6 mm Ø: 200 mm / 12 mm
Sensor handle environmental conditions 0 °C to +50 °C (measuring electronics under control) 0 °C to +50 °C (measuring electronics under control) 0 °C to +50 °C

Shop

TS 410 SDI Anemometer sensor show in Trotec online shop

Technical data

Technical data
General information
  Article number 3.510.220.250
Air flow rate [m/s]
  Min. measuring range | Air flow rate [m/s] 0
  Max. measuring range | Air flow rate [m/s] 20
  Accuracy | Air flow rate [%] 2
  Accuracy ± | Air flow rate [m/s] 0.2
  Resolution | Air flow rate [m/s] 0.01
  Measuring principle | Air flow rate Hot film anemometer
Air temperature [°C]
  Min. measuring range | Air temperature [°C] 0
  Max. measuring range | Air temperature [°C] 50
  Resolution [°C] 0.1
  Accuracy | Air temperature (text) +0.7 °C (v > 0.5 m/s)
Interfaces / plug design
  Plug design SDI connector
Dimensions of sensor element
  Length [mm] 210
  Diameter Ø | Dimensions of sensor element [mm] 6
Material of sensor element
  Stainless steel
  Aluminium
  Composite
  Polycarbonate
  Other
Material of handle
  Material Plastics
  Plastic/metal
  Metal
Surrounding conditions (measuring electronics integrated in handle)
  Min. operating temperature [C] 0
  Max. operating temperature [C] 50
Weight
  (packaging excluded) [kg] 0.097
Ascertainable measured values and functions
Internal sensors
  Air temperature [°F]
  Air flow rate [m/s]
  Air temperature [°C]
  Air volume flow [l/min]
  Air volume flow [m³/h]
  Air volume flow [m³/min]
  Air volume flow [m³/s]
Functions and features
  Plastic probe
  Stainless steel probe

 standard equipment

 optionally available

 not available

Accessories